Integrity & Insulation
 |
With up to 120 & 240 minutes fire resistance |
 |
Integrity & Insulation |
 |
Tested to BS476: Part 20 & FSB/PSB/001/00 requirement |
| VICUCLAD® |
| Board Thickness |
Stability Rating |
Integrity Rating |
Insulation Rating |
| 25mm |
- |
120 minutes |
120 minutes |
| 45mm |
- |
240 minutes |
240 minutes |
|
|

4-sided riser pipes enclosure |
1, 2 and 3-sided Enclosures
3-sided, 2-sided and 1-sided enclosures are constructed in the same way as 4-sided enclosures. Steel angles of 40mm x 40mm x 0.6mm thick are fastened
to the floor soffit or wall with M6 all steel expanding anchors at 600mm nominal centres. The VICUCLAD®
boards forming the walls of the protection to the building services are then fastened to the angles with steel self-tapping screws in appropriate length
at 200mm nominal centres. The services are independently supported.
Wall Penetrations
Where the enclosure passes through a fire compartment wall, the penetration must be properly sealed. The space between the enclosure and the reveal
of the opening in the wall is filled with PROMASEAL® AN Acrylic Sealant.
|