Application  >  E&M Services Enclosures  >  General E&M Services Enclosure  >  PROMATECT®-H
 
   
 
  Hong Kong Singapore Australia Malaysia India
 
Integrity & Insulation

With up to 60, 120 & 240 minutes fire resistance
Integrity & Insulation
Tested to BS476: Part 20 & AS1530: Part 4 requirement
  (Fixing details)

PROMATECT®-H
Board Thickness Stability
Rating
Integrity
Rating
Insulation
Rating
9mm* 60 minutes 60 minutes 60 minutes
15mm 120 minutes 120 minutes 120 minutes
20mm 240 minutes 240 minutes 240 minutes
* Not applicable for Australia

Integrity & Insulation   Steel channel collar at all board joints   External/Internal steel angle fixing   Steel channel framed enclosure

General E&M services enclosure - Integrity & Insulation

General building services include mechanical and electrical services typically used in normal buildings; such as small steel ducts, metal and plastic pipes, electrical and telecommunications cables. As no specific British Standard exists for such application, Promat constructions have been tested in accordance with the criteria of German DIN or British Standard BS476: Part 24, and appraised to BS476: Part 20.

The appraisals include allowance for both internal and external fire. The integrity and where pertinent the insulation performance of the enclosure, and any penetrations through the compartment walls and floors, is measured.

System Specification

General E&M services enclosures are to be constructed using PROMATECT®-H matrix engineered mineral boards all in accordance with the Architectural Specification in the manufacturer’s handbook. Relevant constructions are to be selected according to the required FRL of 60, 120 or 240 minutes of the selected elements. All printed installation details are to be followed to ensure approval to BS476: Part 20 or AS1530: Part 4. All work to be certified by installer in an approved manner.

For more architectural specifications,
continue...

Download full application details in PDF file. PDF download
Integrity Only

With up to 120 minutes & 240 minutes fire resistance
Integrity Only
Tested to BS476: Part 20 requirement
  (Fixing details)

PROMATECT®-H
Board Thickness Stability
Rating
Integrity
Rating
Insulation
Rating
9mm* 120 minutes 120 minutes -
12mm* 240 minutes 240 minutes -
* Not applicable for Australia

Integrity Only   Steel channel collar at all board joints   External/Internal steel angle fixing   Steel channel framed enclosure

General E&M services enclosure - Integrity Only

PROMATECT®-H enclosures provide protection against fire to general building services in accordance with the relevant criteria of BS476: Part 20, for both internal and external fire.

The PROMATECT®-H system featured above ensures integrity of fire compartments.

System Specification

General E&M services enclosures are to be constructed using PROMATECT®-H matrix engineered mineral boards all in accordance with the Architectural Specification in the manufacturer’s handbook. Relevant constructions are to be selected according to the required FRL of 120 or 240 minutes of the selected elements. All printed installation details are to be followed to ensure approval to BS476: Part 20. All work to be certified by installer in an approved manner.

For more architectural specifications,
continue...