External Fire for Circuit Integrity

With up to 120 minutes fire resistance
Integrity & Insulation
Tested to BS476: Part 20 & AS1530: Part 4 requirement

PROMATECT®-H / PROMATECT®-L / PROMATECT®-L500
Stability Rating Integrity Rating Insulation Rating
Circuit integrity

External fire for circuit integrity   3-sided enclosure   2-sided enclosure   Cables & Enclosure support
Inspection opening   PROMASEAL® Ventilation Grille & Promat Ventbox   PROMASEAL® Ventilation Grille   Opening sealed with PROMASEAL® AN Sealant

Electrical Cable Enclosure - External fire for circuit integrity

Internal Cross Section Table 1:
Equal or smaller than 110mm x 100mm

Lid type Thickness of board for different FRL (minutes) Board type
30 60 90 120
Fixed 24mm 45mm 60mm 75mm PROMATECT®-H
Fixed 25mm 40mm 60mm 80mm PROMATECT®-L or
PROMATECT®-L500
Loose fit 25mm 45mm 60mm 80mm

Internal Cross Section Table 2:
Equal or greater than 110mm x 100mm /
Equal or smaller than 520mm x 250mm

Lid type Thickness of board for different FRL (minutes) Board type
30 60 90 120
Fixed 20mm 40mm 50mm 65mm PROMATECT®-H
Fixed 20mm 35mm 50mm 70mm PROMATECT®-L or
PROMATECT®-L500
Loose fit 20mm 40mm 60mm 70mm
FRL = Fire Resistance Levels
PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500

The board thicknesses given in the tables 1 & 2 will ensure that when the duct is exposed to a fully developed cellulosic external fire (BS476 curve), the cable jacket temperature rise will not exceed 120°C and the cables will remain functional. If the cables are not required to maintain circuit integrity it may be possible to reduce the board thickness after consultation with the Promat Technical Department. Promat can also advise on specifications for larger duct sizes. The board thickness is dependent on the internal dimensions of the duct and whether the duct has a loose fit lid or a fixed lid.

Wall penetrations
Wall penetrations

System Specification

Electrical cable enclosures are to be constructed using PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 matrix engineered mineral boards all in accordance with the Architectural Specification in the manufacturer’s handbook. Relevant constructions are to be selected according to the required FRL of 30/60/90/120 minutes of the selected elements. All printed installation details are to be followed to ensure approval to BS476: Part 20 or AS1530: Part 4. All work to be certified by installer in an approved manner.

For more architectural specifications,
continue...