For concrete floors, partitions or walls

With up to 240 minutes fire resistance
Integrity & Insulation
Tested to BS476: Part 20 & AS1530: Part 4 requirement

PROMASTOP® Unicollar®
Stability Rating Integrity Rating Insulation Rating
- 240 minutes 240 minutes
Insulation criteria will vary depending on type and size
of the pipes, and type of penetrating elements.

UniCollar® dimensions   UniCollar® FRL up to -/240/240    

PROMASTOP® UniCollar® dimensions

PROMASTOP® Unicollar®

PROMASTOP® UC Unicollar® is one of a new generation of fire collars designed to protect uPVC, HDPE, PP and other plastic pipes which pass through fire rated elements of building construction. The product has been tested and approved to the relevant criteria of most international standards which include AS1530: Part 4, BS476: Part 20 and has UL Certification for FRL up to 240 minutes. Tests in accordance with EN standards are available upon request.

PROMASTOP® Unicollar® is packed in a box which contains a 2250mm length of collar (150 segments). The box has the installation details printed on one face. Fixing accessories are included. The collar is designed so that it can be cut and snapped in segments of 15mm. For instance, one box is the equivalent of five x 110mm outer diameter (OD) collars. Note that at the time of publication, test data is available for pipe sizes up to 200mm. Please consult Promat Technical Department for more details.

Download full application details in PDF file. PDF download
 
 


Dimension Guide

Pipe size
nominal (OD)
(mm)
(inches)
43
1.24
50
1.5
56
-
63
2
69
-
75
2.5
83
-
90
3
110
-
114
4
125
-
140
5
160
6
200
-
 Casing segments 15 17 18 18 20 21 22 24 25 29 30 33 36 40
 Approx. collars per box 10 8.5 8 7.5 7.5 7 6.5 6 6 5 5 4.5 4 3.75
 Brackets per collar 2* 2* 2* 2* 2* 3 3 3 3 3 3 5 5 5
All figures in above table are tested on both general floor and wall applications.
* 3 brackets are recommended for framed walls if framing is not available to screw into.
 
 
 