email home
Application  >  Penetration Seals  >  PROMASEAL®  >  Mortar
 
   
 
  Hong Kong Singapore Australia Malaysia India
 
For floors and walls

With up to 240 minutes fire resistance
Integrity & Insulation
Tested to BS476: Part 20 & AS1530: Part 4 requirement

PROMASEAL® Mortar
Areas of
Application
Stability
Rating
Integrity
Rating
Insulation
Rating
Floor - 240 minutes 180 minutes *
Wall - 240 minutes 240 minutes *

* The insulation time is the time to failure measured on the surface of the PROMASEAL® Mortar. In some instances, where insulation measured upon the services is the required criteria, this time to insulation failure can be substantially shorter, e.g. for a steel or copper pipe passing through the barrier. If insulation measured upon the services is the relevant criteria for a specific project, please consult Promat Technical Department to ensure the appropriate performance can be obtained.


Mortar (floor)   Mortar (wall)    

PROMASEAL® Mortar (floor)

PROMASEAL® Mortar

PROMASEAL® Mortar (SM) is a specially formulated, lightweight (density approximately 700kg/m³), hydraulic cement composition supplied as a premixed dry powder. It can be troweled into position for sealing of openings required for the passage of services such as electrical cables/pipes, busways and busbars, telecommunication cables/conduits etc. through floors and walls, thus maintaining the fire resistance of building elements that have been penetrated. It can also be used to seal openings after services have been removed or where no services are present.

PROMASEAL® Mortar has been successfully tested and assessed to AS1530: Part 4 and BS476: Part 20 for fire ratings up to 240 minutes depending on service penetration. Insulation criteria will vary depending upon the penetrating services.

PROMASEAL® Mortar is grey in colour and is packaged in convenient 20kg bags. It can be mixed with varying quantities of clean water for different consistencies.

Recommended Specification

Where appropriate, with or without service penetrations, the specified floor/wall openings should be properly fire stopped using PROMASEAL® Mortar capable of providing fire resistance of -/240/- when tested and assessed in accordance with AS1530: Part 4: 2005 and/or BS476: Part 20: 1987. Installation of any fire stopping product should be carried out according to the manufacturer’s recommendations. Please consult Promat for more details.

Download full application details in PDF file. PDF download
 
 
 