For ceilings/floors & partitions/walls

With up to 240 minutes fire resistance
Integrity & Insulation
Tested to BS476: Part 20 & AS1530: Part 4 requirement

PROMASEAL® FyreStrip
Areas of
Application
Stability
Rating
Integrity
Rating
Insulation
Rating
Ceiling/Floor - 240 minutes 240 minutes *
Partition/Wall - 240 minutes 240 minutes *

* Please consult Promat for information on system meeting the insulation criteria.


FyreStrip dimensions   FyreStrip FRL up to -/240/240    

PROMASEAL® FyreStrip dimensions

Dimension Guide

Code no. FS 20 FS 40 FS 50 FS 80 FS 100
(a) Product depth
90 90 90 100 120
(b) Product width
28 46 56 84 124
(c) Minimum element thickness
For FRL up to -/120/120
For FRL up to -/180/180
For FRL up to -/240/240
120mm
150mm
170mm
(d) Minimum gap width for strip insertion
16 24 32 48 64
Minimum gap width at full compression
12 16 24 36 44
Maximum gap width at full expansion
20 40 50 80 100


NOTE: For joints at the top of hollow block and cavity walls, the cavity must be sealed for a minimum of one course. In 120 minutes framed walls, the FRL can be achieved in joints up to a maximum of 50mm sealed with FS50 type. For situations not covered by the above table, please consult Promat.

PROMASEAL® FyreStrip

PROMASEAL® FyreStrip (SE) is a compressible, flexible, fire resistant seal which is used where movement joints are formed in the structure of building. It consists of layers of intumescent material bonded to a special foam and has been successfully fire tested up to 240 minutes in joints within masonry or concrete walls and concrete floors in accordance with the relevant criteria of BS476: Part 20, AS1530: Part 4 and AS4072: Part 1.

PROMASEAL® FyreStrip is available in the following dimensions:
FS20 – 90mm x 28mm x 1000mm;
FS40 – 90mm x 46mm x 1000mm;
FS50 – 90mm x 56mm x 1000mm;
FS80 – 100mm x 84mm x 1000mm;
FS100 – 120mm x 124mm x 1000mm.

The strips are ideal for sealing movement joints at junctions between compartment walls and floors. Their flexibility makes them suitable for use in a variety of configurations. The fire performance of PROMASEAL® FyreStrip will vary according to the particular application. In addition, the width of the gap into which the strip is inserted, as well as their orientation, will have an effect on the level of protection required.

Recommended Specification

Where appropriate, the specified joints and gaps on floor/wall should be properly fire stopped using PROMASEAL® FyreStrip capable of providing a fire resistance of -/240/- when tested and assessed in accordance with AS1530: Part 4 and/or BS476: Part 20: 1987. Installation of any fire stopping product should be carried out according to the manufacturer’s recommendations. Please consult Promat for more details.

Download full application details in PDF file. PDF download
 
 
 
   © Copyright 2010 Promat International (Asia Pacific) Ltd. All rights reserved.