PromaSnap® Floor Waste System
Floor wastes in wet areas are notoriously difficult to seal in the event of a fire. The lack of a pipe stack above the floor
level means that the floor grate offers little protection from fire and smoke once the pipe work has burnt through.
AS4072: Part 1 demands that the fire resistance test of floor wastes must be conducted on pipe work that is identical to the
installed configuration. PromaSnap® Floor Waste System has been
tested for floor waste applications to AS1530: Part 4 and AS4072: Part 1 for 120 minutes with uPVC pipe and fittings.
PromaSnap® Floor Waste System has been designed to not only
provide a tested system but also provide an effective, simple solution for water proofing and the leveling of the screed for
tiling and water flow from the floor.
The system consists of a PROMASEAL® PipeSeal to hold pipe work
in place. If the slab depth is over 125mm deep, the length of pipe required is 75mm less than the slab thickness, e.g. for
a 300mm slab depth a 225mm length of pipe is required.
For slabs less than 125mm thick, reduce the length of the spigot on the PromaSnap® Floor
Waste System that connects to the pipe. To ensure the puddle flange is level, it may be prudent to cut the pipes slightly
less than this 75mm.
PromaSnap® is manufactured entirely from recycled and recyclable
material. PromaSnap® Floor Waste System is certified under the
WaterMark Certification Scheme.
|
Download full application details in PDF file. |
 |
|