For concrete floors only

With up to 240 minutes fire resistance
Integrity & Insulation
Tested to BS476: Part 20 & AS1530: Part 4 requirement

PROMASEAL® Green Cast-in Collar
Stability Rating Integrity Rating Insulation Rating
- 240 minutes 240 minutes
Insulation criteria will vary depending on type and size
of the pipes, and type of penetrating elements.

Green Cast-in Collar dimensions   PROMASEAL® Green Cast-in Collar    

PROMASEAL® Green Cast-in Collar dimensions

Dimension Guide

Code no. uPVC pipe nom. (mm) Body (mm) Flange (mm)
H D1 D2 D3
Green 40 40 49 + 30* 43 115 160
Green 50 50 49 + 30* 56 115 160
Green 65 65 49 + 20* 69 115 160
Green 80 80 60 + 20* 83 163 210
Green 100 100 60 + 20* 110 163 210
* Additional height of upright pipe grip

PROMASEAL® Green Cast-in Collar

PROMASEAL® Green Cast-in Collars are designed to be fixed to formwork prior to pouring of concrete floor slabs. The collar accommodates the uPVC pipe fitting inside the soffit of the slab, enabling significant space savings to be achieved.

PROMASEAL® Green Cast-in Collars will close both pipe and pipe fitting in the event of fire. These collars have been tested for up to 240 minutes in accordance with AS1530: Part 4 and AS4072 with uPVC and some HDPE pipes. PROMASEAL® Green Cast-in Collars provide integrity only criteria when tested to AS1530: Part 4 and AS4072: Part 1 for uPVC floor waste traps of 50mm and 80mm diameters, in accordance with BCA DTS C3, Clause 3.15(b).

For slabs that use lost formwork or are less than 120mm thick, please contact Promat Technical Department.

PROMASEAL® Green Cast-in Collar

Download full application details in PDF file. PDF download
 
 
 