email home
Application  >  Penetration Seals  >  PROMASEAL®  >  Wall Collar
 
   
 
  Hong Kong Singapore Australia Malaysia India
 
For partitions or walls

With up to 120 minutes fire resistance
Integrity & Insulation
Tested to BS476: Part 20 & AS1530: Part 4 requirement

PROMASEAL® FCW Wall Collar
Stability Rating Integrity Rating Insulation Rating
- 120 minutes 120 minutes
Insulation criteria will vary depending on type and size
of the pipes, and type of penetrating elements.

FCW Wall Collar dimensions   Wall Collars can be positioned at an angle    

PROMASEAL® FCW Wall Collar dimensions

Dimension Guide

Code no. Pipe nom.
(mm)
Body (mm)
H D1 D2
FCW 40 40 120 80* 47
FCW 50 50 120 93* 60
FCW 65 65 120 107* 75
FCW 80 80 120 126* 89
FCW 100 100 120 153* 116
FCW 150 150 120 203* 164
* Additional allowance 3mm for clip

PROMASEAL® FCW Wall Collar

PROMASEAL® FCW Wall Collars is designed for insertion into wall elements made of calcium silicate, plasterboard, concrete or masonry, and have been tested on uPVC and HDPE pipes for up to 120 minutes fire rating in accordance with AS1530: Part 4, AS4072: Part 1 and BS476: Part 20. Similar to FC or FCS, this is a split type collar enabling retro fitting where necessary.

PROMASEAL® Wall Collars can be positioned at an angle providing exposure is the same as in the original test. Please contact Promat for details.

PROMASEAL® FCW Wall Collars

Download full application details in PDF file. PDF download
 
 
 
   © Copyright 2010 Promat International (Asia Pacific) Ltd. All rights reserved.