PROMASEAL® FCS Retrofit Collar (circular base)
PROMASEAL® FCS Retrofit Collars are designed to be fitted around installed pipes that
pass through floor slabs and have been tested with uPVC, HDPE and ABS pipes in accordance with the criteria of AS1530: Part 4: 1997 and AS4072: Part 1,
on pipes up to 150mm diameter.
The large opening in the collars will accommodate pipes (and UPVC pipe fittings) that have differing outside diameters.
The collars should be unclipped, placed around the pipe, re-clipped and pushed tight to the substrate.
PROMASEAL® FCS Retrofit Collars have been tested for up to 240 minutes of FRL in floors
with uPVC pipes and ABS pipes, and 180 minutes in floors with HDPE pipe (except 100mm which is tested to 240 minutes), and on floors and walls for
Post Mix drink lines for 120 minutes.
PROMASEAL® FCS Retrofit Collars are designed to split open, enabling them to be retrofitted
when necessary.
IMPORTANT: Always check with Promat Technical Department to ensure the collar under consideration is appropriate for the type, diameter and
thickness of the plastic pipe, and the application and orientation are covered by relevant certification.
|
Download full application details in PDF file. |
 |
|