SQUARE BASE
For ceilings, concrete floor slabs, walls, partitions


With up to 240 minutes fire resistance
Integrity & Insulation
Tested to BS476: Part 20 & AS1530: Part 4 requirement

PROMASEAL® FC Retrofit Collar (square base)
Stability Rating Integrity Rating Insulation Rating
- 240 minutes 240 minutes
Insulation criteria will vary depending on type and size
of the pipes, and type of penetrating elements.

FC Retrofit Collar square type dimensions   For pipes up to 162mm diameter   For pipes up to 162mm diameter with mortar backfill   For pipes up to 162mm diameter with acrylic sealant on ceiling

PROMASEAL® FC Retrofit Collar (squre base) dimensions

Dimension Guide

Code no. Pipe nom.
(mm)
Body (mm) Flange (mm)
H D1 D2 D3
FC 40 40 43 45 77 112
FC 50 50 43 58 90 125
FC 65 65 43 71 103 138
FC 80 80 43 85 123 158
FC 100 100 53 112 150 185
FC 125 125 63 127 165 197
FC 150 150 73 162 200 235
FC 250* 250 120 254 316 380
FC 300* 300 160 318 402 466
* FC with circular base

PROMASEAL® FC Retrofit Collar (square base)

PROMASEAL® FC Retrofit Collars are multi-purpose collars designed for use with concrete slabs, masonry and lightweight walls and lined ceilings.

These split type collars can be retrofited when necessary. They are available in a range of sizes to suit plastic pipes up to 315mm outside diameter*. The collars have been tested for up to 240 minutes FRL in accordance with the criteria of AS1530: Part 4 and AS4072: Part 1 with various types and sizes of plastic pipe.

PROMASEAL® FC Retrofit Collars above 200mm have circular base, not square.

PROMASEAL® FC Retrofit Collars are designed to split open, enabling them to be retrofitted when necessary.

*The FRL for some of the larger collars is restricted in some types of application. It should therefore be clearly noted that, before using any collar with diameter in excess of 110mm, users are encouraged to consult Promat to ensure the proposed application and requisite FRL can be achieved.

IMPORTANT: Always check with Promat Technical Department to ensure the collar under consideration is appropriate for the type, diameter and thickness of the plastic pipe, and the application and orientation are covered by relevant certification.