The following are standard Architectural Specifications for internal partition systems using PROMATECT®-H.
The designer must determine the suitability of the design to the application and requirements before undertaking or constructing any works relating to the
specifications and where in doubt should obtain the advice of a suitably qualified engineer.
|
Fire Attack From Either Side / Non Loadbearing |
![]() |
|
60 minutes of fire rating, integrity and insulation in accordance with the criteria of BS476: Part 22: 1987 and AS1530: Part 4: 2005.
|
| |
|
Acoustic Performance |
![]() |
|
The partition system shall have a Weighted Sound Reduction Index of R w 35.
|
| |
|
Supporting Structure |
![]() |
|
Care should be taken that any structural element that the partition system is supported from, e.g. concrete/brick wall, has equivalent fire
resistance of 60 minutes.
|
| |
|
Lining Boards |
![]() |
|
Four layers of 9mm PROMATECT®-H matrix engineered mineral boards as manufactured by
Promat International (Asia Pacific) Ltd. Each successive layer of board must be fastened to the previous layers at 300mm centres.
|
| |
|
Fixing
|
![]() |
|
Galvanised steel frame made of perimeter steel angle 40mm x 40mm x 1mm thick will be fastened to the wall/floor/ceiling with 40mm x M6 masonry
anchors at 600mm centres. First layer, fixed to perimeter angle using 30mm x No.8 screws at 200mm centres. Each successive layer of board must be
fastened to the previous layers at 300mm centres.
|