Application  >  Partitions & External Walls  >  External Wall Partition  >  PROMATECT®-H  >  Both Sides (Single layer)
 
   
 
  Hong Kong Singapore Australia Malaysia India
 
Both sides - Horizontal sheeting with strip joint -
Fire attack from either side / Non-loadbearing


With up to 120 minutes minutes fire resistance
Integrity & Insulation

PROMATECT®-H
Board Thickness Stability
Rating
Integrity
Rating
Insulation
Rating
9mm - 30 minutes 30 minutes
9mm - 60 minutes 60 minutes
9mm - 120 minutes 120 minutes

For more architectural specification.
continue...

System Specification

Walls are to be constructed using PROMATECT®-H matrix engineered mineral boards all in accordance with the Architectural Specification in the manufacturer’s handbook. Relevant constructions are to be selected according to the required FRL of (.../.../...). All printed installation details are to be followed to ensure approval to BS476: Part 22 and AS1530: Part 4. All work to be certified by installer in an approved manner.



Download this full application detail on PDF version. PDF download

External wall   Horizontal sheeting with strip joint - Non-loadbearing   Typical sections fixing detail  

External wall - Fire attack from either side / Non-loadbearing
Fire Rating
  FRL   -/30/30
-/60/60
-/120/120
  STANDARD   BS476: Part 22: 1987
AS1530: Part 4: 2005
  APPROVAL   BRE CC231705
Acoustic
  # STC


# R w
  38dB (for -/30/30)
47dB (for -/60/60)
48dB (for -/120/120)

38dB (for -/30/30)
46dB (for -/60/60)
47dB (for -/120/120)
  STANDARD   ISO140: Part 3: 1996
ISO717: Part 1: 1996
  PREDICTED
ASSESSMENT
  Marshall Day
18th October 2006
Construction
  MAXIMUM LENGTH   Unlimited
  PARTITION THICKNESS From 242mm
  PARTITION MASS*   From 23.72kg/m² (for -/30/30)
From 25.56kg/m² (for -/60/60)
From 29.22kg/m² (for -/120/120)
# Margin of error is generally within ±3dB.  
*
Details for walls above 3000mm high are available on request.
 
 
 
 