Application  >  Partitions & External Walls  >  External Wall Partition  >  PROMATECT®-H  >  Conversion Wall (Both Sides)
 
   
 
  Hong Kong Singapore Australia Malaysia India
 
Conversion of external to internal wall
Both sides - Horizontal sheeting with strip joint -
Fire attack from either side / Non-loadbearing


With up to 120 minutes fire resistance
Integrity & Insulation

PROMATECT®-H
Board Thickness Stability
Rating
Integrity
Rating
Insulation
Rating
9mm - 30 minutes 30 minutes
9mm - 60 minutes 60 minutes
9mm - 120 minutes 120 minutes

For more architectural specification.
continue...

System Specification

Walls are to be constructed using PROMATECT®-H matrix engineered mineral boards all in accordance with the Architectural Specification in the manufacturer’s handbook. Relevant constructions are to be selected according to the required FRL of (.../.../...). All printed installation details are to be followed to ensure approval to BS476: Part 22 and AS1530: Part 4. All work to be certified by installer in an approved manner.




Download this full application detail on PDF version. PDF download

Conversion of External to Internal wall   Horizontal sheeting with strip joint - Non-loadbearing   Typical sections fixing detail  

Conversion of External to Internal wall - Fire attack from either side / Non-loadbearing
Fire Rating
  FRL   -/30/30
-/60/60
-/120/120
  STANDARD   BS476: Part 22: 1987
AS1530: Part 4: 2005
  APPROVAL   WARRES 38396
Acoustic
  # STC
# R w
  37dB
37dB (-7)
  STANDARD   ISO140: Part 3: 1996
ISO717: Part 1: 1996
  PREDICTED
ASSESSMENT
  Marshall Day
18th October 2006
Construction
  MAXIMUM LENGTH   Unlimited
  PARTITION THICKNESS From 238mm
  PARTITION MASS*   From 23.72kg/m² (for -/30/30)
From 25.50kg/m² (for -/60/60)
From 31.22kg/m² (for -/120/120)
# Margin of error is generally within ±3dB.  
*
Details for walls above 3000mm high are available on request.
 
 
 
 