PROMASEAL® FyreStrip

ADVANTAGES

Fire Resistant Flexible Expansion Strip

PROMASEAL® FyreStrip is a highly compressible, flexible, fire resistant expansion strip seal which is used where movement joints are formed in the structure of a building. It consists of layers of PROMASEAL® Grafitex intumescent material bonded to a special foam and it has been successfully tested for up to 240 minute fire resistance for movement joint seals within concrete/masonry compartment floors and walls (with an equal or greater fire resistance level).

PROMASEAL® FyreStrip is ideal for sealing high movement joints at junctions between compartment walls and floors. Its flexibility makes them suitable for use in a variety of configurations. The fire performance of PROMASEAL® FyreStrip will vary according to the particular application. The width of the gap into which the strip will be inserted as well as the orientation of the strip affect the level of fire resistance provided.

The thickness of PROMASEAL® FyreStrip is determined by the minimum and maximum width of the gap expected during the lifetime of the building. For 240 minute fire resistance, insulation and integrity performance, PROMASEAL® FyreStrip is supplied in the following dimensions:
  1. 1000mm (L) x 28mm (W) x 90mm (D), FS20
  2. 1000mm (L) x 46mm (W) x 90mm (D), FS40
  3. 1000mm (L) x 56mm (W) x 90mm (D), FS50
  4. 1000mm (L) x 84mm (W) x 100mm (D), FS80
  5. 1000mm (L) x 124mm (W) x 120mm (D), FS100
Usage guide
< #Back#

USAGE GUIDE

Code no. FS 20 FS 40 FS 50 FS 80 FS 100
(a) Depth of FyreStrip mm 70*
90
70*
90
90 100 120
(b) Width of FyreStrip mm 28 46 56 84 124
(c) Minimum thickness of penetrating elements mm 170 (-/240/240)
150 (-/180/180)
120 (-/120/120)
170 (-/240/240)
150 (-/180/180)
120 (-/120/120)
170 (-/240/240)
150 (-/180/180)
120 (-/120/120)
170 (-/240/240)
150 (-/180/180)
120 (-/120/120)
170 (-/240/240)
150 (-/180/180)
120 (-/120/120)
(d) Minimum gap width for insertion of FyreStrip mm 16 24 32 48 64
Minimum gap width at full compression mm 12 16 24 36 44
Maximum gap width at full expansion mm 20 40 50 80 100

 

*Up to -/240/- fire resistance in accordance with the requirements of BS 476: Part 20: 1987. Movement joints at the top of the hollow block and cavity walls AND the cavity within the hollow block walls must be sealed for a minimum one layer of PROMASEAL® FyreStrip

USAGE GUIDE

Code no. FS 20 FS 40 FS 50 FS 80 FS 100
(a) Depth of FyreStrip mm 70*
90
70*
90
90 100 120
(b) Width of FyreStrip mm 28 46 56 84 124
(c) Minimum thickness of penetrating elements mm 170 (-/240/240)
150 (-/180/180)
120 (-/120/120)
170 (-/240/240)
150 (-/180/180)
120 (-/120/120)
170 (-/240/240)
150 (-/180/180)
120 (-/120/120)
170 (-/240/240)
150 (-/180/180)
120 (-/120/120)
170 (-/240/240)
150 (-/180/180)
120 (-/120/120)
(d) Minimum gap width for insertion of FyreStrip mm 16 24 32 48 64
Minimum gap width at full compression mm 12 16 24 36 44
Maximum gap width at full expansion mm 20 40 50 80 100

 

*Up to -/240/- fire resistance in accordance with the requirements of BS 476: Part 20: 1987. Movement joints at the top of the hollow block and cavity walls AND the cavity within the hollow block walls must be sealed for a minimum one layer of PROMASEAL® FyreStrip

Health & Safety
< #Back#

HEALTH & SAFETY

No special precautions are required. However, to avoid potential for fibre generation exists, please wear appropriate personal protection gear (safety goggles, protective clothing and dust mask). For more information please check the material safety data sheet, available upon request.

 

WASTE DISPOSAL

Handle as construction industry waste and dispose of in compliance with all local and national regulations in the appropriate and approved manner.

HEALTH & SAFETY

No special precautions are required. However, to avoid potential for fibre generation exists, please wear appropriate personal protection gear (safety goggles, protective clothing and dust mask). For more information please check the material safety data sheet, available upon request.

 

WASTE DISPOSAL

Handle as construction industry waste and dispose of in compliance with all local and national regulations in the appropriate and approved manner.