Duct span maximum up to 10 metres
 |
With up to 120 minutes & 240 minutes fire resistance |
 |
Integrity only |
 |
Tested to BS476: Part 24 & AS1530: Part 4 requirement |
| PROMATECT®-L |
| Board Thickness |
Stability Rating |
Integrity Rating |
Insulation Rating |
| 25mm |
120 minutes |
120 minutes |
- |
| 25mm |
240 minutes |
240 minutes |
- |
Self-supporting ducts provide an economical and fire safe method of constructing natural and
mechanical smoke extract and ventilation ductwork without a steel lining. Lengths of the system
can be prefabricated off-site or constructed on site using the applicable board type. This ensures
that time spent on site is kept to a minimum, with little or no disruption to other trades.

Duct span maximum up to 10 metres wide
For selection of board thickness, it will not only depend on the
required fire performance but also on the internal cross section
of the duct and the operating pressure(s). With large ducts and medium
to high operating pressures, internal stiffeners may be required.
more...
|