Maximum Duct Pressures
The basic construction design is adequate for PROMATECT®-L500
ducts with a maximum internal cross-section of 1200mm x 1200mm for operating
pressures up to ± 500Pa.
This limit can be increased to ± 750Pa if the board thickness is 40mm or greater.
For larger ducts and greater operating pressures, internal stiffeners of either type shown here are required.
Internal Stiffeners
Stiffeners are constructed with strips of minimum 250mm wide PROMATECT®-L500
board and fixed at maximum 600mm centres (Type 1).

Type 1 internal stiffeners
Where a duct is subdivided by a solid PROMATECT®-L500 board, stiffeners are
required with holes cut within the wall of a size and quantity to ensure equal
crossflow of air between the two halves (Type 2).

Type 2 internal stiffeners