PROMATECT®-L500 self-supporting ducts must be supported at maximum 1250mm centres,
located to coincide with joints, or to one side of joint. No protection is required
to the support angle or channel unless each hanger is more than 50mm from the duct sides.
In this case, the support section should be clad as shown above. Vertical duct runs normally
require to be tied back to an adjoining masonry wall using threaded rods and angle or channel
support section at maximum 3000mm centres.

Option fixing
For selection of board thickness, it will not only depend on the
required fire performance but also on the internal cross section
of the duct and the operating pressure(s). With large ducts and medium
to high operating pressures, internal stiffeners may be required.