Application  >  Ductwork  >  Self-supporting Ducts  >  PROMATECT®-L500  >  Board FRL
 
   
 
  Hong Kong Singapore Australia Malaysia India
 
Board Thickness accordance with FRL & Operating Pressure requirements

PROMATECT®-L500  (Type A: Duct exposed to external fire)
Board
Thickness
Stability
Rating
Integrity
Rating
Insulation
Rating
Internal stiffeners
Type 1
Internal stiffeners
Type 2
Max. Duct Pressure
During Fire
25mm  30 minutes 30 minutes 30 minutes - - ± 500Pa 
60 minutes 60 minutes 60 minutes - -
90 minutes 90 minutes 90 minutes - -
120 minutes 120 minutes 120 minutes - -
40mm  30 minutes 30 minutes 30 minutes - - ± 750Pa 
60 minutes 60 minutes 60 minutes - -
90 minutes 90 minutes 90 minutes - -
40mm* 120 minutes 120 minutes 120 minutes - -
52mm* 240 minutes 240 minutes 240 minutes 2 rows 2 rows
40mm  30 minutes 30 minutes 30 minutes - 1 rows ± 1000Pa 
- 2000Pa 
60 minutes 60 minutes 60 minutes - 1 rows
90 minutes 90 minutes 90 minutes - 1 rows
40mm* 120 minutes 120 minutes 120 minutes - 1 rows
52mm* 240 minutes 240 minutes 240 minutes 2 rows -

PROMATECT®-L500  (Type B: Duct exposed to internal fire)
Board
Thickness
Stability
Rating
Integrity
Rating
Insulation
Rating
Type 1
 
Type 2
 
Maximum Duct Pressure
During Fire
25mm  30 minutes 30 minutes 30 minutes - - ± 500Pa 
35mm  60 minutes 60 minutes 60 minutes - -
25mm  240 minutes 240 minutes 30 minutes - -
40mm  30 minutes 30 minutes 30 minutes - - ± 750Pa 
60 minutes 60 minutes 60 minutes - -
90 minutes 90 minutes 90 minutes - -
240 minutes 240 minutes 30 minutes 1 rows 1 rows
40mm  30 minutes 30 minutes 30 minutes - 1 rows ± 1000Pa 
- 2000Pa 
60 minutes 60 minutes 60 minutes - 1 rows
90 minutes 90 minutes 90 minutes - 1 rows
52mm* 120 minutes 120 minutes 120 minutes - 1 rows
52mm  240 minutes 240 minutes 240 minutes 2 rows -
* for performance to AS1530: Part 4, duct constructed 52mm PROMATECT®-L500 boards, external fire (temperature measured
inside duct) FRL 120/120/60. For internal fire FRL 120/120/90. To obtain FRL 120/120/120, use 400mm wide collar.                

For selection of board thickness, it will not only depend on the required fire performance but also on the internal cross section of the duct and the operating pressure(s). With large ducts and medium to high operating pressures, internal stiffeners may be required. Please consult Promat if the operating pressure exceeds 1000Pa.