Type 2 -
Fire attack from above and below / Non-loadbearing


With up to 240 minutes fire resistance
Integrity only
Please consult Promat for ceiling spans details

PROMATECT®-S
Board Thickness Stability
Rating
Integrity
Rating
Insulation
Rating
6.0mm - 120 minutes -
9.5mm - 240 minutes -

Please contact Promat for Architectural Specification to meet specific performance requirements.

System Specification

Self-supporting ceiling membrane systems are to be constructed using PROMATECT®-S a cement/steel composite board are highly resistant to impact and provide excellent resistance to high pressure hose steams during fire. Please contact Promat for more System Specification on required fire resistance.

Download this full application detail on PDF version. PDF download

Type 2   Fixing details    


Type 2 - Fire attack from above and below
Fire Rating
  FRL*   -/240/-
  STANDARD   BS476: Part 22: 1987
  APPROVAL*   BRE CC214487

Acoustic
  # STC
# R w
  29dB
29dB
  STANDARD   ISO140: Part 3: 1996
ISO717: Part 1: 1996
  PREDICTED
ASSESSMENT
  Marshall Day
23rd August 2007

Construction
  CEILING THICKNESS   From 106mm
  CEILING MASS   From 20.07kg/m³

#
*