Type 3 -
Fire attack from below / Non-loadbearing


With up to 240 minutes fire resistance
Integrity only
Please consult Promat for ceiling spans details
  (Steel framing system, Perimeter details & control joints)

PROMATECT®-H
Board Thickness Stability
Rating
Integrity
Rating
Insulation
Rating
9mm - 240 minutes -

For more architectural specification.
continue...

System Specification

Suspended ceiling systems are to be constructed using PROMATECT®-H matrix engineered mineral boards all in accordance with the Architectural Specification in the manufacturer’s handbook. Relevant constructions are to be selected according to the required FRL -/240/- minutes of the selected elements. All printed installation details are to be followed to ensure approval to BS476: Part 22. All work to be certified by installer in an approved manner.

Download this full application detail on PDF version. PDF download

Type 3   Fixing details    


Type 3 - Fire attack from below
Fire Rating
  FRL   -/240/-
  STANDARD   BS476: Part 22: 1987
  APPROVAL   LPC TE89437

Acoustic
  # STC
# R w
  27dB
27dB
  STANDARD   ISO140: Part 3: 1996
ISO717: Part 1: 1996
  PREDICTED
ASSESSMENT
  Marshall Day
16th August 2007

Construction
  CEILING THICKNESS   41mm
  CEILING MASS   From 10.92kg/m³

#

Margin of error is generally within ±3dB.
Deeper air cavity generally improves acoustic performance.

 
 
 
 